BRAND : GENSET PERKINS

Alternator Specifications:

  1. Type: Direct coupling, AVR
  2. Alternator Brand: Selain Stamford
  3. Frequency: 50 Hz
  4. Voltage: 220 / 380 V
  5. Phase / Power Factor: 3 / 0,8
  6. Prime Output Power: 500 KVA (400.000 Watt)
  7. Max. Output Power: 550 KVA(440.000 Watt)

Perkins Engine Specifications:

  1. Type: Diesel 4 stroke
  2. Perkins Engine Model: 2506C-E15TAG2
  3. Cooling System: Water cooled
  4. Aspiration & Cooling: Turbocharged & air to air charge cooled
  5. Compression Ratio: 16 : 1
  6. Cylinder - Arrangement: 6 - Inline
  7. Bore x Stroke: 137 x 171 mm
  8. Total Displacement: 15,2 L
  9. Engine Power Output at Max. Power: 495 kWm / 664 HP
  10. Fuel Consumption: 76 L/h (at 75% Load); 100 L/h (at 100% Load)
  11. Fuel Tank Capacity: minimum for 8 hours operation
  12. Total Oil Lubricating Capacity: 62 L
  13. Coolant Capacity (Engine Only): 58 L

Control System: AMF (Auto Main Failure) Control Module

Genset Specifications:

  1. Genset Protection: control module & MCCB output protection, over voltage, under voltage, over frequency, under frequency, overload, short circuit, high water temperature, and low oil pressure.
  2. Approx. Genset Dimension: 3,394 x 1,449 x 2,05 m (open type); 4,903 x 1,538 x 2,447 m (silent type)
  3. Approx. Genset Weight: 3767 Kg (open type); 5052 Kg (silent type)

 

*) Specifications are subject to change without notice



Spesifikasi

For Generator
Prime Output (kVa) 500 KVA
Maximum Output (kVa) 550 KVA
Serial No.
Model WP550P
For Engine
Model 2506C-E15TAG2
Brand ENGINE PERKINS
For Alternator
Model -
Brand GENERATOR SELAIN STAMFORD